Low Voltage Power Supply Reactive Power Compensation Cabinet Components

Low Voltage Power Supply Reactive Power Compensation Cabinet Components

Details
As a fundamental Low voltage power supply reactive power compensation cabinet components, the CJ19C single-phase series contactor is a specialized device designed for switching low-voltage single-phase capacitors or for split compensation in three-phase capacitor banks. It is a core element within automatic compensation equipment used for reactive power correction.
Category
Low-Voltage Apparatus
 
Send Inquiry
Description
Technical Parameters

As a fundamental Low voltage power supply reactive power compensation cabinet components, the CJ19C single-phase series contactor is a specialized device designed for switching low-voltage single-phase capacitors or for split compensation in three-phase capacitor banks. It is a core element within automatic compensation equipment used for reactive power correction. This essential product is suitable for integration into AC power systems with a frequency of 50Hz and a rated working voltage up to 220V, capably making and breaking connections to capacitor loads up to 90kvar to facilitate effective power factor improvement. This single-phase capacitor switching contactor is an improved and refined design manufactured by our facility, building upon the foundation of the original CJ19C (16C) model. To ensure seamless performance and compatibility as a Low voltage power supply reactive power compensation cabinet components, it must be applied under the following standard operational and installation parameters: a) Ambient air temperature should range from a lower limit of -5°C to an upper limit of +40°C, with the average value calculated over a 24-hour period not surpassing +35°C. b) The altitude of the cabinet installation location must not exceed 2000m. c) Humidity conditions within the cabinet environment should be controlled; at an air temperature of +40°C, the relative humidity must not be more than 50%.

Moreover, the monthly average minimum temperature of the wettest month should be no higher than +25°C, and that month's average maximum relative humidity should remain below 90%. d) The component is intended for use in environments classified as pollution degree 3. e) Its installation category is III. f) The contactor must be mounted inside the cabinet in a position that is not subject to significant shaking, impact, or vibration. g) The mounting surface for this product should not be inclined more than 5° from the vertical. The functional principle, critical for cabinet design, is shown in Figure 1. The schematic above the dotted line represents the switching circuit, and below it is the single-phase capacitor bank. The incorporated resistor switching circuit, featuring early-make contacts in series with resistors, activates first upon coil energization. This path allows the capacitors to charge through the current-limiting resistors, thereby damping the switch-on inrush current. Following this, the main contacts close to carry the continuous capacitive current. A significant durability feature of this Low voltage power supply reactive power compensation cabinet components is the automatic disengagement and reset of the resistor circuit after it completes its inrush suppression task. This greatly reduces the chance of resistor burnout during capacitor disconnection, enhancing the overall reliability, safety, and service life of the components within your low-voltage power supply reactive power compensation cabinet.

product-439-704

Internal Connections and Terminal Markings

 

CJ19C Single-Phase and Three-Phase Y-Type (requires three contactors) Wiring diagram is shown in Figure 2.

The CJ19C (Single-Phase)-43 contactor has two auxiliary contacts, with three combinations.

Auxiliary contact combinations are shown in Table 1. Auxiliary modules can be installed on both sides of the contactor to increase the number of auxiliary contacts.

product-1039-765

 

Two types of auxiliary contacts are available:

LA8-DN11 (one normally open and one normally closed)

LA8-DN20 (two normally open); selected by the user when ordering.

 

Contactor Model

Auxiliary Contact

Normally Open (NO)

Normally Closed (NC)

CJ19C(Single phase)-43

20E

2

-

02E

-

2

11E

1

1

Controlled capacitor 400V

Capacity Qn kvar

20kvar

Rated current InA

87A

Operating current 1.3 In A

113A

Conventional heating current IthA

130A

Suppression of inrush capacity

20 In

Coil

Operating voltage 50Hz Us V

220,380 According to user needs

Range of motion

0.85~1.1Us

Power consumptionVA

Start

115

Absorption

11

Short circuit protection fuse rated current selection

1.5~2.5In

Rated insulation voltage UiV

690V

Auxiliary contact for heating current AC 15 A

10A

Mechanical life

1000000 times

Electrical life operating frequency120 1/h

100000 times

Weight

about 0.6kg

 

External Dimensions and Installation Dimensions

The CJ19C (single-phase)-43 contactor can be installed using M4 screws and lock washers, or using a 35mm mounting rail.

See Figure 3 for the external dimensions and installation dimensions of the CJ19C (single-phase)-43 contactor.

product-955-730

Qualification

product-794-1123
product-794-1123
product-794-1123
product-794-1123
product-794-1123
product-794-1123
product-794-1123
product-794-1123
product-794-1123
product-794-1123
product-794-1123
product-794-1123
product-794-1123
product-793-1125
 

 

Hot Tags: low voltage power supply reactive power compensation cabinet components, China low voltage power supply reactive power compensation cabinet components factory, Reactive Power Compensation Control Cabinet Contactor, Programmable Contactor, Low Voltage Capacitor Contactor, Contactor for Capacitor Bank, AC Contactor Accessories, Capacitive Contactor with Damping Resistor

Send Inquiry
Contact usif have any question

You can either contact us via phone, email or online form below. Our specialist will contact you back shortly.

Contact now!