The series of Power System Contactors is engineered for dependable operation within broader electrical distribution and control networks. These products are designed for use in AC circuits with a frequency of 50Hz and a rated operational voltage up to 660V, capable of switching rated operational currents as high as 95A (for 3-phase systems ≤440V). They fulfill the essential function of remotely connecting and disconnecting circuits, a critical task in power system management. Furthermore, these Power System Contactors are well-adapted for the frequent control of AC motors commonly found in industrial power systems. Under utilization category AC-4 with a suitably reduced current, they can also be employed for challenging duties like the plugging and reversing of squirrel-cage motors. To ensure comprehensive protection within the power system, these products can be effectively combined with thermal overload relays. This partnership helps protect circuits from damage due to sustained operational overloads, enhancing overall system safety and equipment longevity. The operational stability of a Power System Contactor depends on adherence to its specified environmental limits: a) Ambient air temperature must be between ≥-5°C and +40°C, with a daily average not above +35°C. b) The installation altitude should not exceed 2000m. c) At +40°C, relative humidity must be ≤50%. The wettest month's average minimum temperature is ≤+25°C, and its average maximum relative humidity is ≤90%. d) It is designed for pollution degree 3 environments. e) Installation category is III. f) It must be mounted in a location absent of significant shaking, impact, or vibration. g) The mounting surface should be within 5° of vertical. Built to meet the rigorous demands of power system applications, this series of products offers a reliable and robust switching solution for a wide range of electrical infrastructure projects.
Internal Connections and Terminal Markings


External shape and installation dimensions
|
Contactor Model |
Auxiliary Contact |
Normally Open (NO) |
Normally Closed (NC) |
|||
|
CJX2-5011 |
11 |
1 |
1 |
|||
|
Rated operating currentIe |
AC3 |
50A |
||||
|
380V |
AC4 |
24A |
||||
|
Conventional heating current IthA |
80A |
|||||
|
Controllable three-phase squirrel-cage motor powerP kW AC3 |
220V |
15 |
||||
|
380V |
22 |
|||||
|
660V |
33 |
|||||
|
Rated insulation voltage UiV |
690V |
|||||
|
Operating frequency 1/h |
Electrical life |
AC3 |
600 |
|||
|
AC4 |
300 |
|||||
|
Mechanical life |
3600 |
|||||
|
Electrical life |
AC3 |
600000times | ||||
|
AC4 |
150000times | |||||
|
Mechanical life |
8000000times | |||||
|
Coil |
Operating voltageUs 50Hz V |
36/110/127/220/380 |
||||
|
Range of motion |
0.85~1.1Us |
|||||
|
Power ConsumptionVA(50Hz) |
Start |
200 |
||||
|
Absorption |
20 |
|||||
|
Auxiliary contact for heating current AC15 |
10A |
|||||
|
Weight |
about 1.14Kg |
|||||
|
A max |
B max |
C max |
a |
b |
Φ |
Install (Image 2) |
|
79 |
128 |
116 |
40 |
100/110 |
6.5 |
Install using M6 screws and lock washers, or use 35mm or 75mm mounting rails. |
|
Auxiliary Contact Assembly Model |
Auxiliary Contact |
Quantity |
|
|
Normally Open (NO) |
Normally Closed (NC) |
||
|
F4 |
11 |
1 |
1 |
|
20 |
2 |
- |
|
|
02 |
- |
2 |
|
|
22 |
2 |
2 |
|
|
40 |
4 |
- |
|
|
04 |
- |
4 |
|
|
31 |
3 |
1 |
|
|
13 |
1 |
3 |
|
Qualification