Power System Contactor

Power System Contactor

Details
The series of Power System Contactors is engineered for dependable operation within broader electrical distribution and control networks. These products are designed for use in AC circuits with a frequency of 50Hz and a rated operational voltage up to 660V, capable of switching rated operational currents as high as 95A (for 3-phase systems ≤440V).
Category
Low-Voltage Apparatus
 
Send Inquiry
Description
Technical Parameters

The series of Power System Contactors is engineered for dependable operation within broader electrical distribution and control networks. These products are designed for use in AC circuits with a frequency of 50Hz and a rated operational voltage up to 660V, capable of switching rated operational currents as high as 95A (for 3-phase systems ≤440V). They fulfill the essential function of remotely connecting and disconnecting circuits, a critical task in power system management. Furthermore, these Power System Contactors are well-adapted for the frequent control of AC motors commonly found in industrial power systems. Under utilization category AC-4 with a suitably reduced current, they can also be employed for challenging duties like the plugging and reversing of squirrel-cage motors. To ensure comprehensive protection within the power system, these products can be effectively combined with thermal overload relays. This partnership helps protect circuits from damage due to sustained operational overloads, enhancing overall system safety and equipment longevity. The operational stability of a Power System Contactor depends on adherence to its specified environmental limits: a) Ambient air temperature must be between ≥-5°C and +40°C, with a daily average not above +35°C. b) The installation altitude should not exceed 2000m. c) At +40°C, relative humidity must be ≤50%. The wettest month's average minimum temperature is ≤+25°C, and its average maximum relative humidity is ≤90%. d) It is designed for pollution degree 3 environments. e) Installation category is III. f) It must be mounted in a location absent of significant shaking, impact, or vibration. g) The mounting surface should be within 5° of vertical. Built to meet the rigorous demands of power system applications, this series of products offers a reliable and robust switching solution for a wide range of electrical infrastructure projects.

 

Internal Connections and Terminal Markings

product-934-761
product-961-766

 

External shape and installation dimensions 

Contactor Model

Auxiliary Contact

Normally Open (NO)

Normally Closed (NC)

CJX2-5011

11

1

1

Rated operating currentIe

AC3

50A

380V

AC4

24A

Conventional heating current IthA

80A

Controllable three-phase squirrel-cage motor powerP kW AC3

220V

15

380V

22

660V

33

Rated insulation voltage UiV

690V

Operating frequency 1/h

Electrical life

AC3

600

AC4

300

Mechanical life

3600

Electrical life

AC3

600000times

AC4

150000times

Mechanical life

8000000times

Coil

Operating voltageUs 50Hz V

36/110/127/220/380

Range of motion

0.85~1.1Us

Power ConsumptionVA(50Hz)

Start

200

Absorption

20

Auxiliary contact for heating current AC15

10A

Weight

about 1.14Kg

 

A max

B max

C max

a

b

Φ

Install (Image 2)

79

128

116

40

100/110

6.5

Install using M6 screws and lock washers, or use 35mm or 75mm mounting rails.

 

Auxiliary Contact Assembly Model

Auxiliary Contact

Quantity

Normally Open (NO)

Normally Closed (NC)

F4

11

1

1

20

2

-

02

-

2

22

2

2

40

4

-

04

-

4

31

3

1

13

1

3

 

Qualification

product-794-1123
product-794-1123
product-794-1123
product-794-1123
product-794-1123
product-794-1123
product-794-1123
product-794-1123
product-794-1123
product-794-1123
product-794-1123
product-794-1123
product-794-1123
product-793-1125
 

 

Hot Tags: power system contactor, China power system contactor factory, Reactive Power Compensation Control Cabinet Contactor, Programmable Contactor, Low Voltage Capacitor Contactor, Contactor for Capacitor Bank, AC Contactor Accessories, Capacitive Contactor with Damping Resistor

Send Inquiry
Contact usif have any question

You can either contact us via phone, email or online form below. Our specialist will contact you back shortly.

Contact now!